Example 3: Temperature Drop Across Valve(Click on the images for a larger version)The gas analysis and inlet conditions of 1440 psi at 60°F in an inlet separator are known. The pressure safety valve pops at 1440 psi to the flare header. Calculate the temperature of the gas downstream of the PSV (constant enthalpy flash). A. Temperature-Pressure Flash Step 1: Set the "Initial Conditions":
Step 2: Enter "Input Stream":
Step 3: "Execute Flash". Step 4: From the calculated "Data", read the "Enthalpy" of -1.96374E+4 cal/mol. B. Pressure-Enthalpy Flash Step 5: Reset the "Initial Conditions":
Step 6: From the calculated "Data", read the "2-Phase Flash Results at Temperature" of -63.9°F (constant enthalpy flash). This will be the outlet temperature of the relief valve.
|
|||
| ||||
|
|